ما هو مقطع الكابل؟
Cable cross-section is the area of the conductive metal part of the cable, expressed in mm². A larger cross-section reduces resistance and voltage drop but increases cost and installation space.
The value must be selected according to the real operating conditions, not by habit or a single current value.
لماذا يجب اختيار مقطع الكابل بشكل صحيح؟
Undersized cables overheat and create voltage drop, while oversized cables increase cost and complicate panel wiring. Correct sizing balances safety, performance and economy.
العوامل المؤثرة في مقطع الكابل
التيار
Continuous load current and starting current are key inputs.
Length
Longer lines increase resistance and voltage drop.
Voltage drop
The load-side voltage must remain within acceptable limits.
Ambient temperature
High temperature reduces current-carrying capacity.
Installation method
Tray, conduit, buried or open-air installation changes cooling.
Cable type
Insulation, conductor material and number of cores matter.
Grouping
Cables installed together heat each other and need derating.
Protection device
The breaker or fuse must protect the cable properly.
أهمية هبوط الجهد
Voltage drop is especially important in long feeders, motor circuits and sensitive equipment.
| Condition | Possible effect | Engineering response |
|---|---|---|
| Long cable run | Low voltage at the load | Increase cross-section or revise supply point |
| Motor feeder | Hard starting and overheating | Check starting current and allowed drop |
| Lighting circuit | Reduced light level | Split circuits or increase section |
| Sensitive load | Unstable operation | Use tighter voltage-drop limits |
مخاطر اختيار مقطع غير مناسب
Overheating
Insulation ages faster and fire risk increases.
High voltage drop
Motors and devices may operate poorly.
Energy loss
Higher resistance means higher operating cost.
Protection mismatch
Fuses or breakers may not protect the cable correctly.
Difficult installation
Oversized cables can complicate terminals and routing.
مقارنة بين كابل النحاس والألمنيوم
Copper is compact and highly conductive; aluminium is lighter and can be economical in large sizes.
| المعيار | Copper | Aluminium |
|---|---|---|
| Conductivity | Higher | Lower; larger section usually needed |
| Weight | Heavier | Lighter |
| Connection | Common and practical | Needs suitable lugs and tightening practice |
| Cost | Usually higher | Often economical for large feeders |
| Typical use | Panels, machines, compact wiring | Long feeders and large distribution lines |
المقاطع الشائعة ومجالات الاستخدام
The values below are only indicative. التيار capacity changes with installation method, ambient temperature, cable type, number of loaded cores and grouping.
| Section | Approx. current capacity | Typical use |
|---|---|---|
| 1.5 mm² | 10 - 16 A | Lighting and auxiliary circuits |
| 2.5 mm² | 16 - 25 A | Socket and small power circuits |
| 4 mm² | 25 - 32 A | Small motors and sub-feeders |
| 6 mm² | 32 - 40 A | Medium power circuits |
| 10 mm² | 45 - 63 A | Machine feeders |
| 16 mm² | 63 - 85 A | Sub-panels and motor feeders |
| 25 mm² | 85 - 115 A | Distribution feeders |
| 35 mm² | 110 - 145 A | Main or sub feeders |
| 50 mm² | 140 - 180 A | High-current distribution |
توصيات عملية
Start with the load
Clarify current, simultaneity and future additions.
Check the distance
A section sufficient for a short run may fail by voltage drop in a long run.
Define installation
Tray, conduit, buried and panel wiring have different cooling.
Coordinate protection
The protective device must match the cable rating.
Leave service space
Plan bending radius, terminals and labels.
Verify by standards
Compare the result with IEC/TS tables and manufacturer data.
معايير IEC و TS
Standards and manufacturer data must be used for final verification.
| Reference | Scope |
|---|---|
| IEC 60364 | Low-voltage electrical installations and cable selection rules |
| TS HD 60364 | National implementation for low-voltage installations |
| IEC 60228 | Conductor classes and conductor properties |
| Manufacturer catalogues | التيار ratings by cable type and installation method |
الخلاصة
Cable sizing must consider current capacity, voltage drop, installation conditions, ambient temperature, cable material and protective devices together. Calculations should be checked against relevant standards and manufacturer tables.
حساب مقطع الكابل
حساب مقطع الكابل
اختيار مقطع الكابل قرار أساسي لسلامة المنشأة وكفاءة الطاقة. المقطع الصحيح يقلل السخونة وهبوط الجهد وفقد الطاقة ومخاطر الأعطال.
FAQ
Can cable size be selected only by current?
No. Distance, voltage drop, installation method, temperature, cable type and grouping must also be considered.
Why is voltage drop important?
It can reduce equipment performance, cause motor problems and increase energy loss.
Copper or aluminium?
Copper is compact and conductive; aluminium is lighter and economical for large feeders.
What data is needed?
التيار, voltage, phase, length, allowed voltage drop, conductor material, installation method, temperature and grouping.