Technische Informationen

Ratgeber zur Auswahl des Kabelquerschnitts

Die Auswahl des Kabelquerschnitts ist entscheidend für Sicherheit und Energieeffizienz. Der richtige Querschnitt reduziert Erwärmung, Spannungsfall, Verluste und Ausfallrisiken.

Was ist der Kabelquerschnitt?

Cable cross-section is the area of the conductive metal part of the cable, expressed in mm². A larger cross-section reduces resistance and voltage drop but increases cost and installation space.

The value must be selected according to the real operating conditions, not by habit or a single current value.

Warum muss der Kabelquerschnitt richtig gewählt werden?

Undersized cables overheat and create voltage drop, while oversized cables increase cost and complicate panel wiring. Correct sizing balances safety, performance and economy.

Einflussfaktoren auf den Kabelquerschnitt

Strom

Continuous load current and starting current are key inputs.

Length

Longer lines increase resistance and voltage drop.

Voltage drop

The load-side voltage must remain within acceptable limits.

Ambient temperature

High temperature reduces current-carrying capacity.

Installation method

Tray, conduit, buried or open-air installation changes cooling.

Cable type

Insulation, conductor material and number of cores matter.

Grouping

Cables installed together heat each other and need derating.

Protection device

The breaker or fuse must protect the cable properly.

Bedeutung des Spannungsfalls

Voltage drop is especially important in long feeders, motor circuits and sensitive equipment.

ConditionPossible effectEngineering response
Long cable runLow voltage at the loadIncrease cross-section or revise supply point
Motor feederHard starting and overheatingCheck starting current and allowed drop
Lighting circuitReduced light levelSplit circuits or increase section
Sensitive loadUnstable operationUse tighter voltage-drop limits

Risiken eines falschen Kabelquerschnitts

Overheating

Insulation ages faster and fire risk increases.

High voltage drop

Motors and devices may operate poorly.

Energy loss

Higher resistance means higher operating cost.

Protection mismatch

Fuses or breakers may not protect the cable correctly.

Difficult installation

Oversized cables can complicate terminals and routing.

Vergleich von Kupfer- und Aluminiumkabeln

Copper is compact and highly conductive; aluminium is lighter and can be economical in large sizes.

KriteriumCopperAluminium
ConductivityHigherLower; larger section usually needed
WeightHeavierLighter
ConnectionCommon and practicalNeeds suitable lugs and tightening practice
CostUsually higherOften economical for large feeders
Typical usePanels, machines, compact wiringLong feeders and large distribution lines

Häufige Querschnitte und Anwendungen

The values below are only indicative. Strom capacity changes with installation method, ambient temperature, cable type, number of loaded cores and grouping.

SectionApprox. current capacityTypical use
1.5 mm²10 - 16 ALighting and auxiliary circuits
2.5 mm²16 - 25 ASocket and small power circuits
4 mm²25 - 32 ASmall motors and sub-feeders
6 mm²32 - 40 AMedium power circuits
10 mm²45 - 63 AMachine feeders
16 mm²63 - 85 ASub-panels and motor feeders
25 mm²85 - 115 ADistribution feeders
35 mm²110 - 145 AMain or sub feeders
50 mm²140 - 180 AHigh-current distribution

Praktische Empfehlungen

Start with the load

Clarify current, simultaneity and future additions.

Check the distance

A section sufficient for a short run may fail by voltage drop in a long run.

Define installation

Tray, conduit, buried and panel wiring have different cooling.

Coordinate protection

The protective device must match the cable rating.

Leave service space

Plan bending radius, terminals and labels.

Verify by standards

Compare the result with IEC/TS tables and manufacturer data.

IEC- und TS-Normen

Standards and manufacturer data must be used for final verification.

ReferenceScope
IEC 60364Low-voltage electrical installations and cable selection rules
TS HD 60364National implementation for low-voltage installations
IEC 60228Conductor classes and conductor properties
Manufacturer cataloguesStrom ratings by cable type and installation method

Fazit

Cable sizing must consider current capacity, voltage drop, installation conditions, ambient temperature, cable material and protective devices together. Calculations should be checked against relevant standards and manufacturer tables.

Kabelquerschnitt berechnen

Kabelquerschnitt berechnen

Die Auswahl des Kabelquerschnitts ist entscheidend für Sicherheit und Energieeffizienz. Der richtige Querschnitt reduziert Erwärmung, Spannungsfall, Verluste und Ausfallrisiken.

Rechner öffnen

FAQ

Can cable size be selected only by current?

No. Distance, voltage drop, installation method, temperature, cable type and grouping must also be considered.

Why is voltage drop important?

It can reduce equipment performance, cause motor problems and increase energy loss.

Copper or aluminium?

Copper is compact and conductive; aluminium is lighter and economical for large feeders.

What data is needed?

Strom, voltage, phase, length, allowed voltage drop, conductor material, installation method, temperature and grouping.